Download: CTT Serial Cable Test Termination Himalayal.pdf
Mode: CTT-700
One pair
Un rated voltage (KV): 700 r.m.s
PD level (Un, pC): <2
UI rated impulse voltage (KV): Negative polarity: 1650
Max. dimension of power cable (include insulation layer, mm): 160
Power: 220V/20A, 50/60Hz
Max. cooling capacitance (KW): 120
Water capacitance (I): 500
Max. temperature (℃): 60
Max. pressure (atm): 4
Electric conductivity range (us/cm): 0.1-2
Max. ambient temperature (℃): 35
Min. ambient temperature (℃): 3
Max. cooling water temperature (℃): 20
Min. cooling water flow velocity (I/min): 45
Connecting water pipe (in): 1
Water pipe head (in): 3/4
Dimension (mm): 1200*1400*1700
Weight (not include water, kg): 272
Terminal tilt angle: 45°
Dimension (L*W, mm): 5800*1400
Cable mounting height (mm): 1600
Terminal mounting height (mm):5500
Min HV insulation distance (mm): 3300
Terminal weight (two sets together, kg): 650
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.
Himalayal Corporation Limited
Tel:+86 21 5059 9069
Email: info@himalayal.com
http://www.himalayal.com
http://www.himalayal.com.cn