TYDZ-750KVA/0.4KV/0~10.5KV Contact Type Voltage Regulator
Home > Systems > AC Dielectric Test > Regulator Transformer > >350kVA Range

TYDZ-750KVA/0.4KV/0~10.5KV Contact Type Voltage Regulator

Lead time: 60 days

Mode: TYDZ-750KVA/0.4KV/0~10.5KV
Single phase           Frequency: 50Hz          Cooling methods: ONAN
Rated Capacity: 750kVA                                Rated Output Voltage: 0~10.5kV
Regulating methods: Motor drive                 Rated Output Current: 0~71.4A
Rated Input Voltage: 0.4kV                            Aberration Ration of Waveform: ≤3%
Rated Input Current: 1875A                          Starting Voltage ≤1%
Short-circuit Impedance:≤7.5%(in range of 50%~100%, impedance is being linearity)
Mode of Regulation: electrical drive Operation Time:5 min on, 30 min off, 20 cycles per day
Short-circuit capability: When test transformer discharge to the test object via damping resistance under transient state, short-circuit current reach 2 times of rated value. The discharge last 8 circle will no damage regulator’s winding or mechanical distortion.
Insulation Level: 20kV/1min (low voltage winding to earth)
                              5kV/1min (high voltage terminal to ground)
Overload capability: 1.2IH 30min, 1.4IH 15min, 1.6IH 5min.
Product structure: 1. There are upper and lower position limited, oil drain valve, oil level indicator
                                 2. Regulating unit and raise voltage raising units are set together.
contact type voltage regulator contact type voltage regulator

contact type voltage regulator contact type voltage regulator