Mode: TYCZ 200KVA/0.38KV/0~3.15KV
Single phase, 60 Hz Voltage regulating way: electrical drive
Cooling: ONAN Rated capacity: 200KVA
Rated voltage: input voltage: 0.38KV output voltage: 0~3.15KV
Rated current: input current: 909A output current: 0~63.5A
Impedance voltage: ≤7.5% (regulating in the range of 50%-100%)
Starting voltage: ≤1% Waveform distortion: ≤3% Noise level: ≤60db
Working time: working for 60 min under 100% rated voltage and current
Short circuit ability: Under temporary capacity when output side of test transformer discharge to test object by protecting resistor, short circuit current is more than 2 times output. Discharging time lasting for 8 wave cycles should not cause any heat damage and mechanical distortion to regulator winding.
Structure: equip with upper and lower limit function, oil drain valve and oil indicator;
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.
Himalayal Corporation Limited
Tel:+86 21 5059 9069
Email: info@himalayal.com
http://www.himalayal.com
http://www.himalayal.com.cn