Mode: TYDZ‐250kVA/0.38kV/0~3.15kV
Single phase Rated Input Current: 657.9A
Frequency: 50Hz Rated Output Voltage: 0~3.15kV
Rated Capacity: 250kVA Rated Output Current: 0~79.4A
Rated Input Voltage: 0.38kV Aberration Ration of Waveform:≤3%
Short‐circuit strength: When test object breakdown, the short‐circuit current reach 5 times output, discharge continue 5 cycles no damage to regulator winding or cause any mechanical distortion.
Temperature raise: oil surface temperature raise 55K, winding temperature raise 65K.
Note: include ‐ magnetism oil surface indicator, servo motor driving device, position indicator with terminal contacts and protection contacts.
Operation Time: working for 60 min under 100% rated voltage and current.
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.
Himalayal Corporation Limited
Tel:+86 21 5059 9069
Email: info@himalayal.com
http://www.himalayal.com
http://www.himalayal.com.cn