150kVA ~ 350kVA Range
TYDZ 250kVA/0.38KV/0~0.63KV Contact Type Voltage Regulator
Home > Systems > AC Dielectric Test > Regulator Transformer > 150kVA ~ 350kVA Range

TYDZ 250kVA/0.38KV/0~0.63KV Contact Type Voltage Regulator

Lead time: 60 days

Mode: TYDZ 250kVA/0.38KV/0~0.63KV
Single phase          Frequency: 50Hz                Cooling methods: ONAN
Rated Capacity: 250kVA                                    Rated Output Voltage: 0~6.3kV
Regulating methods: Motor drive                    Rated Output Current: 0~39.7A
Rated Input Voltage: 0.38kV                              Aberration Ration of Waveform: ≤3%
Rated Input Current: 657.9A                              Starting Voltage ≤1.5%
Short-circuit Impedance:≤7.5%(in range of 50%~100%,impedance is being linearity)
Mode of Regulation: electrical drive
Operation Time: 15 min on, 15 min off, 48 cycles per day
Short-circuit capability: When test transformer discharge to the test object via damping resistance under transient state, short-circuit current reach 2 times of rated value. The discharge last 8 circle will no damage regulator’s winding or mechanical distortion.
Over load capability: withstand 30min at 1.2 IH; withstand 15min at 1.4IH; withstand 5min at 1.6IH
Product structure: 1. There are upper and lower position limited, oil drain valve, oil level indicator
                                 2. Regulating unit and raise voltage raising units are set together.
contact type voltage regulator contact type voltage regulator

contact type voltage regulator contact type voltage regulator

Principle Diagram: 