150kVA ~ 350kVA Range
TYDZ-300kVA/0.4kV/0~3.15kV Contact Type Voltage Regulator
Home > Systems > AC Dielectric Test > Regulator Transformer > 150kVA ~ 350kVA Range

TYDZ-300kVA/0.4kV/0~3.15kV Contact Type Voltage Regulator

Lead time: 60 days

Mode: TYDZ-300kVA/0.4kV/0~3.15kV
Single phase                     Frequency: 50Hz             Rated Capacity: 300kVA
Rated Input Voltage: 0.4kV                                        Rated Output Current: 0~95.2A
Rated Input Current: 750A                                          Aberration Ration of Waveform: ≤3%
Rated Output Voltage: 0~3.15kV                              Starting Voltage ≤1 %
Short-circuit Impedance:≤7.5%(in range of 50%~100%,impedance is being linearity)
Cooling: ONAN Noise level: <65dB (Measured in one meter)
Mode of Regulation: electrical drive
Operation Time: working for 60 min under 100% rated voltage and current
Insulation level:
      5kV/1min Primary winding to secondary winding and earth
      10kV/1min secondary winding to primary winding and earth
Overload capability: withstand 30min at 1.2IH, 15min at 1.4IH, 5min at 1.6IH.
Note: include - magnetism oil surface indicator, servo motor driving device, position indicator with terminal contacts and protection contacts.
The symmetrical compensation and reversed polarity voltage regulation circuit is adopted so that output voltage of the regulator keeps smooth and linearity, and regulating speed can be set and to be very stable. The interlock between voltage regulator, control table and secondary switch are available.
 contact type voltage regulator contact type voltage regulator

contact type voltage regulator contact type voltage regulator

Principle Diagram: 